Ask your supplierCan you cut a session now, everywhere, and is the plant still safe afterwards?
Where it happens
On the access path, this failure sits at the highlighted stage.
Failure and fix
- Fails like this (illustrative, not a reported incident)
- An operator ends a suspicious session and the console shows it as disconnected, but the vendor's client is attached through a second node and keeps sending input. In OT, a session is cut in the middle of a firmware transfer and the device is left half-written.
- Good looks like
- Enforced termination within an agreed deadline. External input ends at once; any safe completion is done by the local operator under an agreed procedure.
Real incidents
This failure has happened. Below are examples on public record, from government advisories, court records and legislative records. They are the ones found so far, not a count of how often it happens. Victims, vendors and products are not named here; the source has the detail.
No incident on public record found yet. That does not mean it has not happened. The example above is illustrative.
Know one? Tell usIn OT
SP 800-82r3 says a remote disconnect should not impact OT operations. Agree per zone what stops at once and who finishes the current step, and test it on a test system or in an approved window. (SP 800-82r3 App. F, AC-17(9) OT discussion; 6.2.4.1)
How the core tests check it
Each test tries the failure on purpose. It passes only if the failure is stopped or detected.
Repeat termination while the client is disconnected or a session/control node is partitioned.
Enforcement meets D_stop at every relevant boundary; a console status alone is insufficient evidence.
Keep an interactive session open and run an approved harmless long operation across grant end and idle-session timeout; after each event, send harmless keystrokes or commands from the external session.
No external input reaches the target after grant end or timeout. Only the completion step named in the safe-stop contract finishes, performed by the named local party or within E_finish without new external input authority. Stopping access is not misreported as undoing work already started.
Apply termination during a simulated OT maintenance operation with an agreed local operator.
The documented safe-stop/finish-current-operation behavior is observed and recorded; safety controls remain effective.
Mapped to
What this item draws on. The mapping is the author's reading; see BASIS.md.
Controls
- SP 800-53 AC-17(9)
- SP 800-53 MA-4(e)
- SP 800-82r3 6.2.10
MITRE ATT&CK®
No technique is mapped. This failure is about authorization logic, which ATT&CK does not describe as a technique.
Requirements tested
- P10Supervision and response
- P08Time-limited grants
- P21OT-safe enforcement
Industry practice
S13 CIP-005-7 R2 Parts 2.4-2.5: methods to determine and to disable active vendor remote access sessions; R3 Part 3.2: terminate vendor-initiated remote connections and control the ability to reconnect. S11: physical disconnect when not in use; operator warning when a vendor connects.
Further reading
Where to read more on this failure, from the sources this suite cites.